High Voltage Probes

for Oscilloscopes

TT-HVP 08 | 1000:1

Attenuation Ratiox1000
AccuracyVDC ±2 % [+5 kV]
±3 % [+5 kV-8 kV]
VAC ±3 % @ 1 kHz
Input Impedance100 MΩ, 3 pF
Bandwidth40 MHz (-3 dB)
Rise Time9 ns
Cable Length2.0 m
Compensation Range10..30 pF
Max. Input VoltageDC 8 kV, AC 6 kVrms, PEAK 16 kV
Dimensions (L x W x H)220 mm x 50 mm x 50 mm
IEC61010-031: 2015CAT I Pollution Degree 2
Datasheet
Order number15008

TT-HVP 15HF | 1000:1

TT-HVP 15HF - Order number: N2771B
Attenuation Ratiox1000
AccuracyVDC ±6 %
VAC ±6 % @ 1 kHz
Input Impedance100 MΩ, 1 pF
Bandwidth50 MHz (-3 dB)
Rise Time7 ns
Cable Length2.0 m
Compensation Range15..30 pF
Max. Input VoltageDC 15 kV, AC 10 kVrms, PEAK 30 kV
Dimensions (L x W x H)350 mm x 75 mm x 75 mm
IEC61010-031: 2015CAT I Pollution Degree 2
Order number15000

TT-HVP 15 B | 1000:1

TT-HVP 15B - Order number: N2771B
Attenuation Ratiox1000
AccuracyVDC ±6 %
Input Impedance100 MΩ, 3 pF ±0.5 pF
Bandwidth40 MHz (-3 dB)
Rise Time≤8.8 ns
Cable Length2.0 m
Compensation Range15..30 pF
Max. Input VoltageDC 10 kV, AC 7 kVrms, PEAK 20 kV
Dimensions (L x W x H)350 mm x 75 mm x 75 mm
IEC61010-031: 2015CAT 0
Datasheet
Manual
Order number15010

TT-HVP 2739 | 1000:1

Attenuation Ratiox1000
AccuracyVDC ±3 %
VAC ±6 % @ 1 kHz
Input Impedance900 MΩ, 2 pF
BandwidthDC 50 MHz
Rise Time1.6 ns
Cable Length2.0 m
Compensation Range15..35 pF
Max. Input VoltageDC+AC peak 39 kV, AC 27 kVrms
Dimensions (L x W x H)320 mm x 80 mm x 80 mm
IEC61010-031: 2015CAT I Pollution Degree 2
Order number15014

for Multimeter

TT-HVP 40 | 1000:1

Attenuation Ratiox1000 @ 10 MΩ
x2000 @ 1 MΩ
Input Impedance1000 MΩ
Bandwidth300 Hz (-3 dB)
Cable Length1,0 m
Max. Input VoltageDC 40 kV, AC 28 kVrms (0..300 Hz)
Abmessungen (L x W x H)350 mm x 75 mm x 75 mm
IEC61010-031: 2015CAT I Pollution Degree 2
Datasheet
Manual
Order number15001

All specifications and characteristics are subject to change without notice.